DFW10-12 Cable Branch Box With SF6 Load Switch
Features
◆SF6 Gas Insulation
Utilizes SF6 (Sulfur Hexafluoride) gas for superior arc-extinguishing and insulation, ensuring high safety and long service life.
Maintenance-free design with sealed construction, resistant to harsh environments.
◆Compact & Modular Design
Space-saving structure suitable for compact substations or overhead line applications.
Modular components allow flexible configurations (2-6 branches).
◆Load Switching & Protection
Equipped with SF6 load switch for safe load breaking and isolation.
Can be combined with fuses for overload and short-circuit protection.
◆Wide Applicability
Rated voltage: 12kV
Rated current: 630A (switch), up to 200A per branch.
Suitable for ring main units (RMU), cable branching, and distribution automation systems.
◆Safe & Reliable
IP65 protection rating for dust/water resistance.
Mechanical interlocks prevent misoperation.
Low operating noise and no flammable materials.
Model And Meaning

Conditions Of Use
(1) Altitude: The DFW10-12 cable branch box is within the correct operating range at an altitude of less than 2000m. Customers above 2000m can negotiate with the manufacturer to produce equipment to suit your special environment;
(2) Ambient temperature: The equipment can operate normally at -40~45 degrees. If your DFW10-12 cable branch box has an SF6 compliant switch inside, you need to pay attention to its ability to adapt to ambient temperatures of 15~45 degrees;
(3) Humidity: Under normal ambient temperatures, the daily average humidity is 95% and the monthly average is 90% or less. However, the ambient humidity varies according to the change in ambient temperature, so the actual humidity should be evaluated based on the temperature first;
(4) Earthquake intensity: The impact of earthquake intensity on the equipment is not strong at 8 degrees or below, but it will affect the operation of the equipment after exceeding 8 degrees;
(5) Wind speed: 35m/s or below;
(6) Remind each customer to try to use this product in an environment without severe vibration or other harmful gases.
Main Technical Parameters
| Item | Unit | Load switch unit | Combination electrical unit | Circuit breaker unit | |
| Rated voltage | KA | 12 | 12 | 12 | |
| Insulation level | 1min power frequency withstand voltage | KV | 42/48 | 42/48 | 42/48 |
| Lightning impulse withstand voltage | 75/85 | 75/85 | 75/85 | ||
| Rated current | A | 630/1250 | 125 | 630/1250 | |
| Rated transfer current | 1700 | ||||
| Closed loop breaking current | 630 | ||||
| Cable charging breaking current | 10 | ||||
| 5% rated active load breaking current | 315 | ||||
| Ground fault breaking current | 30 | ||||
| Breaking current of cable charging during ground fault | KA | 17.3 | |||
| Rated short-circuit breaking current | Note 1 | 20 | |||
| Rated closing capacity | 50 | Note 1 | 50 | ||
| Rated withstand current 4S | 20 | 20 | |||
| Rated peak withstand current | 50 | 50 | |||
| Mechanical life (main switch/grounding switch) | 1000/3000 | 1000/3000 | 1000/3000 | ||
Wiring Diagram

Contact us
If you're interested in the DFW10-12 Cable Branch Box with SF6 Load Switch or need technical support, please reach out through Email: pannie@hdswitchgear.com.Let us know your requirements, and we'll provide a tailored solution promptly!
We Can Help:
Product inquiries & quotations
Technical specifications & customization
Installation guidance & maintenance support
OEM/ODM services
Our factory



Our Certificate





Hot Tags: dfw10-12 cable branch box with sf6 load switch, DFW10 12 SF6 Load Break Cable Branch Terminal Enclosure, Hexaflouride Switch Cable Branch Gear, DFW10 12 Load Switch Cable Device, SF6 Load Break Cable Junction Enclosure, High Voltage Cable Splitter Box, High Voltage Cable Splitter Distribution Box