JCZ5 Vacuum Contactor
The JCZ5 series vacuum contactor is a product of our company that has been optimized and inproved based on the original design.It has the advantages of strong breaking ability,small bounce,and long service life.
This product is a three-phase AC 50Hz indoor high-voltage switch control equipment,suitable for power systems with rated working voltages of 7.2KV,12KV and below,and working currents up to 630A.It can control and frequently operate high-voltage electrical equipment and is often used in conjunction with F-C cabinets.It is also widely used in high-voltage capacitor reactive power compensation devices.
Model and meaning

Ambient condition
1 Ambient temperature: max +40°C min -15°C(conveyance under -30°C is allowed)
2 Altitude: ≤1000m
3 Relative humidity: daily average relative humidity: ≤95%; monthly average relative humidity≤90%; daily average saturated vapor pressure ≤2.2*10-3 MPa; monthly average value ≤1.8*10-3 MPa
4 Earthquake intensity: ≤8 degree
5 The installation should be free from fire, explosion, severe vibration, chemical corrosion and serious pollution
Technical Parameter
|
name |
unit |
numerical value |
|||
|
Rated voltage |
kV |
7.2(12) |
7.2(12) |
7.2(12) |
7.2(12) |
|
Rated current |
A |
160 |
250 |
400 |
630 |
|
Rated frequency |
Hz |
50 |
50 |
50 |
50 |
|
Power frequency withstand voltage |
32(42) |
32(42) |
32(42) |
32(42) |
32(42) |
|
Connection capability |
A/100order |
1600 |
2500 |
4000 |
6000 |
|
On/off capability |
A/25order |
1280 |
2000 |
3200 |
5000 |
|
Ultimate breaking capacity |
A/3order |
3200 |
3200 |
4000 |
6000 |
|
Mechanical lifespan |
one million time |
100 |
100 |
100 |
100 |
|
Opening time |
ms |
≤120 |
≤120 |
≤120 |
≤120 |
|
Closing time |
ms |
≤150 |
≤150 |
≤150 |
≤150 |
|
Contact opening distance |
mm |
4(5)±0.5 |
4(5)±0.5 |
4(5)±0.5 |
4(5)±0.5 |
|
Overtravel |
mm |
≥1.2 |
≥1.2 |
≥1.2 |
≥1.2 |
|
Mechanical lifespan |
one million time |
50 |
50 |
50 |
50 |
|
Electrical lifespan |
order |
300000 |
300000 |
300000 |
300000 |