GW5 Seris Outdoor Three Phase AC High Voltage Disconnecting Switch
GW5 outdoor MV isolating switch is used for three-phase AC 50Hz outdoor high voltage electrical equipment, used for the line to switching under voltage pressed no load condition, and electrical isolation the maintenanced high voltage bus, circuit breakers and other electrical equipment and charged high voltage line, can also be used for the opening and closing small capacitance or inductance current. When the knife in the normal break position, can provide a insulation distance consistent with safety requirements. Widely used in 35~110kV substation.
GW5-40.5, 72.5, 126(W) I 630,1250,1600,2000 Distyle Fracture Level Rotation Outdoor Three Phase AC High Voltage Disconnecting Switch (hereinafter called switch) is supplied to high voltage circuitry for throwover under no load condition, and is used as electric disconnect for overhauled high voltage bus ,breaker and such high voltage electric device and high voltage circuitry with electricity.
GW5 IH Outdoor AC High Voltage Disconnecting Switch conforms to the following standards:
GB1984-89″AC High Voltage Disconnecting Switch and Earthing Switch"
IEC 129(1984)"AC High Voltage Disconnecting Switch and Earthing Switch"
IEC 694(1980)"Shared Terms for High Voltage Switch Devices and Control Devices Standards"
Type and Meaning

Normal usage condition
1. Ambient temperature, -40°C ~+40°C
2. Altitude: not over 2000m
3. Pollution degree: ⅡⅢ Ⅳ
4. Thickness of icing: not over 10m
5. Wind pressure not over 700Pa
6. Earthquake degree: not over 8 degree
7. The place where it is used is free from flammable and explosive danger, chemical corrosion and frequent intense vibration
Main technical data and mechanical feature data
1. main technical data (table 1)
| No. | Product mode Rated value |
GW5-40.5 II | GW5-72.5 Ⅲ | GW5-126 Ⅲ | |||||||||||
| 1 | Rated voltage | 40.5 | 72.5 | 126 | |||||||||||
| 2 | Rated current | 630 | 1250 | 1600 | 2000 | 630 | 1250 | 1600 | 2000 | 630 | 1250 | 1600 | 2000 | ||
| 3 | Disconnecling knife | Rated withstand current(peakvalue) | 50 | 80 | 100 | 100 | 50 | 80 | 100 | 100 | 50 | 80 | 100 | 100 | |
| Rated short-time withstand current(eflective value)kA |
20 | 31.5 | 40 | 40 | 20 | 31.5 | 40 | 40 | 20 | 31.5 | 40 | 40 | |||
| duration of rated short circutt (8) | 4 | ||||||||||||||
| 4 | 1-Shaped aalthing knife |
Rated withstand current(peakvalue) | 25 | ||||||||||||
| Rated shon-time withstand current effective value)kA |
10 | ||||||||||||||
| duration of rated short circuit (s) | 4 | ||||||||||||||
| 5 | 1-Shaped ealthing knife |
Rated withstand current(peak value) | 100 | ||||||||||||
| Rated shornt-time withstand current effective value)kA |
40 | ||||||||||||||
| duration of rated short circuit (S) | 4 | ||||||||||||||
| 6 | Rated short-time power frequency withstand voltage(affective value kV |
To earth | 95 | 160 | 230 | ||||||||||
| Across the isolating distance |
118 | 197 | 265 | ||||||||||||
| 7 | Rated lightning mpulse withstand voltage(effective value kV |
To earth | 185 | 350 | 550 | ||||||||||
| Across the isolating distance |
215 | 385 | 630 | ||||||||||||
| 8 | Rated terminal static mechanical load N |
Level vertical | 750 | 750 | 750 | 750 | 1000 | 1000 | |||||||
| Level horizontal | 500 | 500 | 500 | 500 | 750 | 750 | |||||||||
| vartical force | 500 | 750 | 500 | 750 | 1000 | 1000 | |||||||||
| 9 | Switch generatrix conversion current generatrix conversion voltage 100V)A |
504 | 1000 | 1280 | 1800 | 504 | 1000 | 1280 | 1600 | 504 | 1000 | 1280 | 1600 | ||
| 10 | Wireless electricity disturbing level | no | no | Not over 2000 μ V | |||||||||||
| 11 | Mechanical endurance | 3000 | 3000 | 3000 | |||||||||||
| No | Product modelRated value | GW5-40.5 Ⅲ | GW5-72.5 Ⅲ | GW5-126 Ⅲ | ||||||||||
| 1 | Fracture insulation distance of disconnecting switch after switch-off (≥mm) |
400 | 600 | 1000 | ||||||||||
| 2 | To earth insulation distance of conduclive part (≥mm) |
400 | 600 | 1000 | ||||||||||
| 3 | Main circuit resistance (su 2) | 200 | 150 | 95 | 75 | 220 | 155 | 100 | 80 | 245 | 170 | 110 | 90 | |
| 4 | Closing and opening-simultaneity of 3 phase of man kninl smm |
5 | 8 | 12 | ||||||||||
| 5 | Opening and closing time combined electric motor(s |
CJ6:3.75,CJ2-XG:3±1 | ||||||||||||
| 6 | Weight of Single poles(kg) | 125 | 150 | 160 | 190 | 200 | 240 | |||||||
Products sort
1.Product can be sorted three models according to voltage degree: 40.5kV, 72.5kV, 126kV.
2.Product can be sorted four models according to current degree: 640A, 1250A, 1600A, 2000A,
3. Product can be sorted four models according to attached installing earthing switch: no earthing, left earthing, right earthing, double earthing. The attached installing earthing switch can be sorted two models according to short circuit current capacity: I earthing switch, n earthing switch. And dynamic short-time withstand value of n earthing switch is the same as disconnecting knife's.
Advantages:
Reliable isolation under no-load conditions.
Robust construction for harsh outdoor environments (wind, rain, pollution).
Low maintenance due to simple mechanical design.
Flexible configurations (single or double earth switches possible).
Product structure and Working principle
1. Structure
GW5 IH disconnecting switch(Fig.2, Fig.3) is composed of three single poles, operating mechanism and transmission parts. Each single pole is set in an I – shaped frame, composing of underplate, axletree seat, support insulation, connection seat, left and right contacts, earthing static contact and earthing switch knife and so on.
Main knife of three phase ac switch is combined with CS171V series human mechanism; it also can be combined with CJ6 or CJ2-XG.; earthing knife is combined with CS171V series human mechanism. When human operating mechanism combines with electromagnetic lock, electric interlock among disconnecting switch, earthing switch and breaker can efficient achieved, avoiding incorrect operation.
2.Opening operation
I.Main knife working principle
The operation of gw4 is connected with switch main shaft through vertical transmission rod, joint and universal joint, and connected with each separate single pole through joint and link rod, so that it achieve synchronous act of the three single poles.
3.Earthing knife working principle
Three single-pole earthing knives are connected through three single-pole transmission rods. Main shaft of operating mechanism is connected with one set of space four-connection rods through vertical transmission rod and joint. When the mechanism acts, closing and opening operations of earthing knife are achieved through vertical transmission rod and space four-connection rods.
4.Auxiliary switch working principle
The auxiliary switch of operating mechanism is linked with main shaft of mechanism. Break or close the relevant contacts when act opening or closing, and give the relevant signals.
5.Main, earthing knives mechanical lockout
When both of main, earthing knives are combined with human operating mechanism, the interlock between eathing switch and disconnecting switch is achieved through interlock board of mechanism. When main knife operating mechanism is combined with electric mechanism, the interlock between eathing switch and disconnecting switch is achieved through interlock board between disconnecting switch and earthing knife rotation axis.
Product outline and installation size


Note:There are items from 11-to 15 only with 126kV witage.
fig2. GW5 111 type steel bracket sketch map of three-pole general installation (assembing manual operating machine)

Contact Us
If you're looking to contact a supplier or manufacturer for the GW5 series outdoor three-phase high-voltage disconnecting switch. Let me know how I can assist further!Email:pannie@hdswitchgear.com.
When inquiring, include:
Rated voltage & current (e.g., 35kV, 1250A).
Manual or motorized operation.
Quantity required.
Any special requirements (e.g., extreme weather resistance).
Our factory



Our Certificate





Hot Tags: gw5 seris outdoor three phase ac high voltage disconnecting switch, high voltage separation for power systems, high voltage power separation in electrical circuits, high voltage cut off switch, electrical disconnector for hv systems, high voltage circuit cut off in networks, high voltage circuit disconnector