ERB2L-125 High Breaking Small Leakage Circuit Breaker

ERB2L-125 High Breaking Small Leakage Circuit Breaker

ERB2L-125 series high breaking small leakage circuit breaker is suitable for AC 50/60HZ, rated voltage 400V and single-phase 230V, rated current below 100A circuit, as personal contact protection and equipment leakage protection, with leakage, overload, short circuit and other protection functions, and under normal circumstances, as a line infrequent conversion. Overvoltage protection function can also be added according to user needs.
Send Inquiry
Product Introduction

 

Products Description

 Scope of application


ERB2L-125 series high-breakage small leakage circuit breakers are suitable for AC 50/60HZ, rated voltage 400V and single-phase 230V, rated current below 100A lines, as personal contact protection and equipment leakage protection, with leakage, overload, short circuit and other protection functions, and under normal circumstances, as a line infrequent conversion. Overvoltage protection function can also be added according to user needs.
This product is mainly used for the protection of building lighting and power distribution systems, and has isolation function.
This product complies with standards: IEC60947-2, GB/T14048.2.


 Model and meaning

 

product-665-315

 Structural characteristics
ERB2L-125 series high-breakage small leakage circuit breakers are assembled from ERB2L-125 high-breakage small circuit breakers and leakage releases. The leakage circuit breaker is a current-operated electronic leakage circuit breaker, mainly composed of a zero-sequence current transformer, an electronic component board, a leakage release, and a circuit breaker with overload and short-circuit protection.


 Technical parameters

Rated voltage(V) Frame grade Rated current In(A) Number of poles Neutral line Rated current In(A)

Rated leakage operating current

IΔn(mA)

Rated leakage non-operating current IΔno(mA)

Rated short circuit points

Segment capacity Icu(A)

Overvoltage protection setting value (V) Leakage action time (s) Trip unit type
230 100

1

N 63,80,100,125 30,50,100,200,300 15,25,50,100,150 10000 280±5% ≤0.1 C,D
230 2 /
400 3 /
230/400 3 N

 Tripping characteristics (reference temperature 30°C)

Rated current In(A) Starting State Test current(A) Specified time(t) Expected results
≤63 cold 1.05In t ≧1h No trip
>63 t ≧2h
≤63 hot 1.30In t<1h Trip
>63 t<2h
All values cold 20In t<360s Trip
All values cold Type C 5In t ≧0.1s No trip
Type D 10In
All values cold Type C 10In t<0.1s Trip
Type D 14In

 Appearance and installation dimensions

product-549-416

 

Honor and qualification
1
3
8
4

 

6

 

 

 

 

 Contact Us

 

For more information or to request a quote, please reach out to us at:

austinyang@hdswitchgear.com

rexwang@hdswitchgear.com

pannie@hdswitchgear.com

Hot Tags: erb2l-125 high breaking small leakage circuit breaker, eeprom, proximity sensors, rf oscillators, bipolar transistors, infrared sensors, fiber optic circulators

Send Inquiry

whatsapp

Phone

E-mail

Inquiry