ZW8-12(G) Outdoor High-Voltage Vacuum Circuit Breaker
The ZW8-12(G) series outdoor high-voltage vacuum circuit breaker is a three-phase, 50Hz AC outdoor high-voltage switching device. It consists of an operating mechanism, a conductive circuit, an insulation system, sealing components, and an enclosure, featuring a three-phase common-tank design. It is intended for use in 10kV rural and urban power distribution networks to make and break load currents, overload currents, and short-circuit currents, as well as for other similar applications.
Applicable standards: GB1984-2003 "High-voltage alternating-current circuit-breakers," GB/T 11022-1999 "Common specifications for high-voltage switchgear and controlgear standards," and IEC 62271-100 "High-voltage alternating-current circuit-breakers."

Model and Meaning

Main Technical Parameters
| Project | Unit | Data | |
| Rated voltage | KV | 12 | |
| Rated current | A | 630 1250 | |
| 1-min power frequency withstand voltage | 42 | ||
| Lightning impulse withstand voltage(peak value) | KV | 75 | |
| Rated short circuit breaking current | KA | 16 20 25 | |
| Rated short circuit closing current | 40 50 63 | ||
| Rated peak withstand current | KA | 40 50 63 | |
| 4s short time withstand current | 16 20 25 | ||
| Rated operating sequence | Open - 0.3s - Close/Open - 180s - Close/Open | ||
| Rated short circuit current breaking times | times | 30 | |
| Mechanical life | 10000 | ||
| Rated operating voltage with dedicated spring operating mechanism | trip coil | V | DC or AC 220 |
| closing coil | V | DC or AC 220 | |
| Rated current of overcurrent release device | A | 5 | |
| Allowable wear thickness for fixed and moving contacts | mm | 3 | |
| Contact gap | mm | 11±1 | |
|
Overtravel (contact spring compression) |
mm | ||
| Three pole asynchronous closing and opening | ms | ≤2 | |
| Contact closing bounce time | ms | ≤2 | |
| Average opening speed | m/s | 1.0±0.2 | |
| Average closing speed | m/s | 0.7±0.15 | |
| Opening time | under the highest operating voltage | s | 0.015-0.05 |
| at the lowest operating voltage | s | 0.03-0.06 | |
| Closing time | s | 0.025-0.05 | |
| Main circuit resistance | μΩ | ≤120(with G ≤200) | |
Appearance and installation dimensions

Our factory
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
International cooperation
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
International Exhibitions
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
Our Certificate
![]() |
![]() |
![]() |
![]() |
Contact Us
For inquiries, pricing, or technical specifications regarding the ZW8-12(G) Series Vacuum Circuit Breaker, please contact us:pannie@hdswitchgear.com.
FAQs about ZW8-12(G) Series
Q: What is the main application of this circuit breaker?
A: It is designed for 12kV power distribution systems, mainly used in outdoor rural power grids, industrial enterprises, and substations for switching load and short-circuit currents.
Q: What is the standard control voltage?
A: The standard voltage for both the trip coil and closing coil is DC or AC 220V. Other voltages are available upon request.
Q: Can you supply customized specifications?
A: Yes, we can customize the rated current, breaking capacity, and control voltage according to your project requirements.
Q: How can I get a quotation?
A: Please send your technical requirements or inquiry list to [pannie@hdswitchgear.com]. We will reply within 24 hours.
Hot Tags: zw8-12(g) outdoor high-voltage vacuum circuit breaker, high voltage outdoor vacuum circuit breaker function, high voltage outdoor vacuum circuit breaker quality, high voltage vacuum breaker outdoor testing, outdoor circuit breaker for high voltage vacuum, outdoor circuit breaker high voltage vacuum, outdoor vacuum breaker high voltage feature
You Might Also Like
Send Inquiry