ZW32-12F(G)/ZW32M-12 Outdoor Intelligent (Electronic Watchdog) / Permanent-Magnet Type High-Voltage Vacuum Circuit Breaker
The ZW32-12F(G)/ZW32M-12 series-comprising outdoor intelligent (with electronic "watchdog" functionality) and permanent-magnet type high-voltage vacuum circuit breakers-are designed for three-phase AC 50Hz power systems with a rated voltage of 12kV. These intelligent circuit breakers are primarily used as 10kV outgoing feeders in substations or as line protection switches within 10kV three-phase AC power systems, capable of making and breaking load currents, as well as interrupting overload and short-circuit currents. They fulfill requirements for control, measurement, and metering, while also supporting remote control and monitoring-enabling "four remote" functions (remote control, remote signaling, remote measurement, and remote adjustment).
These circuit breakers comply with technical standards including GB 1984 "High-voltage AC Circuit Breakers," DL/T 402 "Technical Specifications for Ordering High-voltage AC Circuit Breakers," and DL/T 403 "Technical Specifications for Ordering 12kV–40.5kV High-voltage Vacuum Circuit Breakers."
Model and Meaning

Main Technical Parameters
| No. | Project | Unit | Data | ||
| 1 | Rated Voltage | kv | 12 | ||
| 2 | Rated Insulation Level | 1min power frequency withstand voltage | Dry test(for ground,inter electrode/fracture) | 42/48 | |
| wet test | 34 | ||||
| Ligntning impluse withstand voltage(peak,inter pole/fracture) | 75/85 | ||||
| 3 | Rated Current | A | 630 | ||
| 4 | Rated short circuit breaking current | KA | 20 | ||
| 5 | Rated operating sequence | O-0.3S-CO-180S-CO | |||
| 6 | Rated short circuit breaking current breaking times | times | 30 | ||
| 7 | Rated short circuit closing current(peak) | KA | 50 | ||
| 8 | Rated peak withstand current | ||||
| 9 | Rated short time withstand current | 20 | |||
| 10 | Rated short circuit duration | S | 4 | ||
| 11 | Opening time | ms | ≤35 | ||
| 12 | Closing time | ms | ≤40 | ||
| 13 | Mechanical life | times | 10000 | ||
| 14 | Rated closing operation voltage | V | DC24,AC/DC110,220 | ||
| 15 | Rated opening operation voltage | ||||
| 16 | Overcurrent protection | Current setting multiple | 0.2~2.5 | ||
| Alloable deviation of setting current | ±10% | ||||
| Delay setting value | S | 0~5 | |||
| Delay tolerance | ±10% | ||||
| 17 | Quick break protection | Current setting multiple | 2.5~10 | ||
| Alloable deviation of setting current | ±10% | ||||
| Delay setting value | 5 | 0~0.5 | |||
| Delay tolerance | ±10% | ||||
| 18 | Control unit ACcharging input current | Rated value | A | 5 | |
| fluctuation range | A | 0.5~8 | |||
Appearance and installation dimensions

Our factory
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
International cooperation
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
International Exhibitions
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
Our Certificate
![]() |
![]() |
![]() |
![]() |
Contact us
If you are looking for the manufacturer or supplier of ZW32-12 outdoor high-voltage vacuum circuit breaker, here are contact information:pannie@hdswitchgear.com.Let me know your requirements!
Hot Tags: zw32-12f(g)/zw32m-12 outdoor intelligent (electronic watchdog) / permanent-magnet type high-voltage vacuum circuit breaker, high voltage circuit breaker vacuum outdoor specification, high voltage vacuum breaker outdoor specification, high voltage vacuum circuit breakers outdoor supplier, outdoor circuit breaker high voltage vacuum design, vacuum circuit breaker high voltage outdoor installation, vacuum high voltage outdoor breaker performance
You Might Also Like
Send Inquiry