YB Series Prefabricated Substation
YB series prefabricated substation (usually called "box-type substation" or "European box-type substation") is a compact distribution equipment that integrates high-voltage switchgear, transformers, low-voltage distribution devices, etc. in a closed box. It is widely used in urban power grids, industrial and mining enterprises, communities, wind and solar power generation, etc. The following is a detailed introduction to the series:
Model Meaning

Main structural components
High-voltage room: usually equipped with ring network cabinet or terminal cabinet, including load switch, fuse, lightning arrester, etc., supporting 10kV or 35kV voltage level.
Transformer room: install dry or oil-immersed transformers (such as S11, S13 and other energy-saving types), the capacity range is usually 100kVA~2500kVA.
Low-voltage room: equipped with circuit breakers, metering devices, capacitor compensation, etc., output 400V low-voltage power supply.
Box: made of metal (such as stainless steel, color steel plate) or non-metallic materials, with functions such as wind and sand protection, moisture resistance, heat insulation, and anti-theft.
Faeture
◇ High-voltage switchgear, transformer, low-voltage switchgear trinity, strong completeness;
◇ Perfect high and low voltage protection, safe and reliable operation, simple maintenance;
◇ Occupy less land, save investment, short production cycle, and easy to move;
◇ Flexible and diverse wiring schemes;
◇ Structure: honeycomb structure double-layer (composite plate) The shell is firm, heat insulation, heat dissipation and ventilation, beautiful, high protection level, and the shell materials are stainless steel alloy, aluminum alloy, cold-rolled plate, color steel plate are optional;
◇ Various types: general-purpose, villa-type, compact and other styles;
◇ The automatic terminal (FTU) of the assembly network in the high-voltage ring main unit realizes the reliable detection of short circuit and single-phase grounding fault, and has the function of "four remotes", which is convenient for the automatic upgrade of distribution network.
Technical Parameters
| Compartment | Item | Unit | Parameter | ||
| High voltage compartment | Rated frequency | Hz | 50/60 Hz | ||
| Rated Voltage | KV | 3.3KV,6.0KV, 6.6KV | 10KV 11KV 13.8KV 15KV 20KV 22kv |
30KV 33KV 35KV 36KV | |
| Max service voltage | KV | 7.2 KV | 12KV,24KV | 40.5KV | |
| Rated current | A | 400,630,1000,1250,1600,2000,2150,...etc | |||
| Transfer current | A | 1200-3150A | |||
| 1MIN Power frequency withstand voltage,earth-phase | KV | 42/48,85/95 | |||
| 1MIN Power frequency withstand voltage,phase/fracture | |||||
| BIL | KV | 75/85,170/185 | |||
| Rated short circuit breaking current | KA | 20,31.5 | |||
| Transfomer compartment | Rated voltage | KV | 3.3KV,6.0KV 6.6KV | 10KV 11KV 13.8KV 15KV 20KV 22kv | 30KV 33KV 35KV 36KV |
| Rated power capacity | KVA | 200KVA Upto 2.5MVA | |||
| Tapping range | % | ±2X2.5%,±5% | |||
| Vector group | Yyn0,Dyn11 | ||||
| Short-circuit Impedance | % | 4.0,4.2,4.5,6,8 | |||
| Low voltage compartment | rated voltage | V | 220,380,400,415,433,440,660,690,800 | ||
| main circuit rated current | A | 50-4000 | |||
| branch current | A | 5-800 | |||
| *This table is only for a single specification of the product and does not represent the data parameters of all |
Installation conditions
1. Ambient temperature upper limit ≤ 40 ℃ and lower limit ≥ - 10 ℃.
2. Solar radiation ≤ 1000Wm2.
3. Altitude ≤ 1000m.
4. Icing ≤ 20mm.
5. Wind speed ≤ 35m/s.
6. Humidity:
Daily average relative humidity ≤ 95%.
Monthly average relative humidity ≤ 90%.
Daily average relative water vapor pressure ≤ 22kPa.
Monthly average relative water vapor pressure ≤ 1.8kPa.
7. Earthquake ≤ 8 degrees.
8. Places without fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: When the above conditions cannot meet the use requirements,the user shall negotiate with the manufacturer.
① Transformers can be dry-type or oil-immersed.
② The low-voltage chamber has the overall function of low-voltage switchgear,which can be selected and combined arbitrarily by users.
③ Shell material:Composite plate,stainless steel composite plate,aluminum plated zinc plate, stainless steel plate,metal carved plate.
④ Structure characteristics:High voltage structure is reasonable and compact,can choose HXGN17 XGN15 ring network cabinet,ll with five anti interlocking function.The transformer natural ventilation and automatic ventilation cooling system can be used for dry and oil transformers.
⑤ Low-voltage room:Various power distribution schemes can be adopted according to user's requirements,with various functions such as power distribution,lighting distribution,reactive power automatic compensation,electric energy metering,etc.,and equipped with automatic lighting system.
Basic drawing

Maintenance and safety
Regular inspection: fasteners, insulation status, ventilation system.
Dust and moisture proof: especially suitable for dusty or humid areas.
Operation specification: After the high-voltage side is powered off, it is necessary to test the power and discharge before entering the box.
Hot Tags: yb series prefabricated substation, Smart YB Power Facility, Prefab YBW Transformer Yard, Smart Factory Built Hub, Assembled Power Plant, YB Smart Grid Power Shelter, Intelligent Advanced Substation
You Might Also Like
Send Inquiry