FZRN21-40.5D Indoor High Voltage Air Load Break Switch
Technical parameters
| NO. | Items | Unit | Value |
| 1 | Rated voltage | kV | 40.5 |
| 2 | Rated frequency | Hz | 50 |
| 3 | Maximum rated current of fuse | A | 63 |
| 4 | 1min power frequency withstand voltage | kV | 95/110 |
| 5 | Lightning impulse withstand voltage | kV | 185/215 |
| 6 | Rated peak withstand current | kA | 50 |
| 7 | 4S rated short time withstand current | kA | 20 |
| 8 | Rated active load breaking current | A | 1250 |
| 9 | Rated closed loop breaking current | A | 1250 |
| 10 | Rated cable charging breaking current | kA | 21 |
| 11 | Rated short circuit breaking current | kA | 31.5 |
| 12 | Rated short circuit making current | kA | 80(expected peak value) |
| 13 | Mechanical life | times | 10000 |
Technical parameters of vacuum load switch after installation and adjustment
|
No. |
Name |
Unit |
Data |
|
1 |
Contact clearance |
mm |
17 ± 1 |
|
2 |
Compression of contact spring |
mm |
4 ± 1 |
|
3 |
Average closing speed |
m/s |
0.8 ± 0.2 |
|
4 |
Average opening speed (opening distance reaches 6mm) |
m/s |
1.5 ± 0.2 |
|
5 |
Opening time |
ms |
≤ 60 |
|
6 |
Out of simultaneity of CO operations of three poles |
ms |
≤ 2 |
|
7 |
Contact bouncing duration at closing operation |
ms |
≤3 |
|
8 |
Distance between charged bodies and to ground |
mm |
≥300 |
|
9 |
Loop resistance between upper and lower supports |
μΩ |
≤80 |
Technical parameters of isolating switch after installation and adjustment
|
No. |
Name |
Unit |
Data |
|
1 |
Out of simultaneity of closing operation of three poles |
ms |
≤ 2 |
|
2 |
Deflection of just closing position of each pole |
mm |
≤ 2 |
|
3 |
Positive pressure of contact |
N |
260 ± 20 |
|
4 |
Fracture opening distance |
mm |
≥350 |
|
5 |
Loop resistance |
μΩ |
≤150 |
Technical parameters after adjustment of the assembly of earthing switches for combined electrical appliances
|
No. |
Name |
Unit |
Data |
|
1 |
Out of simultaneity of closing operation of three poles |
ms |
≤ 2 |
|
2 |
Deflection of just closing position of each pole |
mm |
≤ 2 |
|
3 |
Positive pressure of contact |
N |
450 ± 40 |
|
4 |
Fracture opening distance |
mm |
≥300 |
Technical Parameters of Fuses for Combination Appliances
| Model | Rated Voltage(kV ) | Rated current of fuse holder(A) | Fuse rated current (A) |
| XRNTЗA | 12 | 16 | 3.15,63,10,16, |
| 40 | 20,25,31.5,40 | ||
| 63 | 50,56,63 |
The use of environmental conditions
1.Air temperature: -25°C~+40°C;
2.Altitude: s1000m;
3.Relative humidity: daily average is not more than 95%,
4.Installation places: No fire, explosion hazard, serious filthy places.
5.Contamination level:ll
Structural characteristics
Combination of appliances for the three-pole linkage structure; mainly by the frame, vacuum interrupter, disconnecting switch (equipped with fuses), grounding switch and spring-operated mechanism composed of disconnecting switch.
Vacuum interrupter and grounding switch through the insulator country set on the frame, spring operating mechanism is mounted on the side plate of the frame.
Principle of operation
◆Operation of vacuum interrupter
Combination of electrical appliances vacuum interrupter room operation mode using electric spring actuator for closing, with the release solenoid for breaking, can also be used for manual closing. When closing manually, the operating handle is used to rotate the spring-operated mechanism's transducer shaft in clockwise direction.
◆Disconnecting switch, grounding switch, split, split operation
The vacuum interrupter, disconnecting switch and earthing switch of the combined appliance are equipped with a reliable mechanical interlocking device, and the disconnecting switch and earthing switch are operated by the same shaft. When the disconnecting switch is closed, the vacuum load switch is closed at last. The order of separation is reversed, and the isolating and earthing switches can be operated only when the vacuum load switch is in the tripping state.
◆Fuse impingement release tripping
When a short-circuit current or overcurrent flows through the main circuit of a combined appliance in the closing position, at least one phase of the fuse fuse is blown. Impactor action, tripping speed depending on the size of the current, the larger the current, the faster the speed of tripping, so that the combination of electrical mechanical release device action, so that the vacuum interrupter in the action of the tripping spring to achieve a reliable and rapid tripping.