ZN85- 40.5 Indoor High Voltage Vacuum Circuit Breaker

ZN85- 40.5 Indoor High Voltage Vacuum Circuit Breaker

Product model: ZN85-40.5/T2000-31.5
Rated voltage: 40.5kV
Applicable power system: 3-phase AC 50Hz
Operation structure: Upper and Lower Layout
Insulation structure: Composite insulation structure, using three independent epoxy resin insulating tubes to isolate the three-phase disconnector and related live parts
Air separation and creepage distance requirements: Compliant
Send Inquiry
Product Introduction

Introducing the ZN85-40.5/T2000-31.5 Indoor High Voltage Vacuum Circuit Breaker (referred to as VCB), a cutting-edge solution tailored for 3-phase AC 50Hz power systems with a rated voltage of 40.5kV. Specifically designed to handle load currents, overload currents, and fault currents, this VCB is indispensable for mining enterprises, power plants, and substations.

ZN85- 405 indoor high voltage vacuum circuit breaker

 

This breaker boasts an innovative upper and lower layout for its operation structure, effectively reducing its depth. Ensuring a high level of safety, the 3-phase interrupter and associated live parts are isolated by three independent epoxy insulating tubes, forming a composite insulation structure. This configuration not only meets air distance and creepage distance requirements but also significantly minimizes the overall size of the VCB. The leading electric circuit interrupter, static and dynamic conductive connections are ingeniously housed within the insulating tube, reducing the phase distance to a mere 300mm. The fixed-type leading electric circuit enhances stability, and the insulating tube is expertly installed on the upside of the frame.

No.

Item

Unit

Data

 

Rated voltage

kV

40.5

2

Rated Current

A

1250 160020002500 31504000

3

Rated frequency

Hz

50

4

Rated short circuit breaking current

kA

25

31.540

5

Rated Short-Circuit switching current(peak)

63

80

6

4S rated short-circuit withstand current

25

31.5

7

Rated peak withstand current

63

80

8

1 min power frequency withstand voltage

95

9

Lightning impulse withstand voltage(peak)

kV

185

10

Rated operating sequence

 

分-0.3S-CO-180S-CO

0-0.3S-CO-180S-CO

11

Rated short-circuit current breaking times

 

Times

20

12

Mechanical life

10000

13

Breaking time

ms

≤80

14

Single capacitor bank breaking current

A

630

15

Back to back capacitor bank breaking current

A

400

16

Rated operating voltage

V

-100/~110,-220~200

 

A specially designed spring actuator, seamlessly integrated into the frame, is a unique feature of this VCB. This design, tailored for the upper and lower structure, is an integral and inseparable part of the VCB. The overall design is simple, ensuring a more suitable output curve that aligns with the distinctive features and requirements of the 40.5kV VCB.

With a well-thought-out and aesthetically pleasing layout, this VCB stands out for its compact size, flexible endurance, ease of inspection, and maintenance-free operation. It is exceptionally suitable for frequent operations and can thrive in challenging environments, making it an ideal choice for locations with poor conditions. Embrace a circuit breaker that not only performs reliably but also embodies sophistication and practicality.

 

Fixing type external shape &installation dimensions

Fixing type external shape installation dimensions

Remarks:

1.The cabinet width is 1.4m;The travel of the propulsion mechanism is 610mm.

2.Left grounding,right tool-receiving interlock,with S8/S9 position switch,and no left and right stroke switch touch plates.

3.Intermediate outlet,58-core secondary socket,and 1.4m secondary hose length.

4.Operating voltage DC220V.

5.Other requirements shall be subject to the contents confirmed in the order selection table.6.Technical parameters are subject to the instruction manual.

Rated current(A)

630

1250

1600

2000

2500

3150

4000

Rated short-circuit breaking current (kA)

25,31.5

31.5,40

Size of mating stationary contact (mm)

φ35

φ49

φ55

φ79

φ90

φ109

 

General appearance &installation dimensions

General appearance installation dimensions

Remarks:

1.The cabinet width is 1.4m;The travel of the propulsion mechanism is 610mm.

2.Left grounding,right tool-receiving interlock,S8/S9 position switch,no left and right stroke switch touch plates.

3.Intermediate outlet,58-core secondary socket,and 1.4m secondary hose length.

4.Operating voltage DC220V.

5.Other requirements shall be subject to the contents confirmed in the order selection table.6.Technical parameters are subject to the instruction manual.

Rated current(A)

630

1250

1600

2000

2500

3150

4000

Rated short-circuit breaking current (kA)

25,31.5

31.5,40

Size of mating stationary contact (mm)

φ35

φ49

φ55

φ79

φ90

φ109

 

Outline dimension drawing of plateau handcart type solid seal

Outline dimension drawing of plateau handcart type solid seal

Remarks:

1.When the altitude is≤3000m,the pole spacing is 400,and when the altitude is>3000m,the pole spacing is 472. 2.The cabinet width is 1.68m;The travel of the propulsion mechanism is 610mm.

3.Left grounding,right tool-receiving interlock,with S8/S9 position switch,and no left and right stroke switch

4(to)Inte(uch)rmediat(plates.)e outlet,58-core secondary socket,and 1.4m secondary hose length.

5.Operating voltage DC220V.

6.Other requirements shall be subject to the contents confirmed in the order selection table.

7.Technical parameters are subject to the instruction manual.

Rated current(A)

630

1250

1600

2000

2500

3150

4000

Rated short-circuit breaking current (kA)

25,31.5

31.5,40

Size of mating stationary contact (mm)

φ35

φ49

φ55

φ79

φ90

φ109

 

Hand-drawn outline and dimension drawing

Hand-drawn outline and dimension drawing

Remarks:

1.The cabinet width is 1.68m;The travel of the propulsion mechanism is 610mm.

2.Left grounding,right tool-receiving interlock,with S8/S9 position switch,and no left and right stroke switch touch plates.

3.Intermediate outlet,58-core secondary socket,and 1.4m secondary hose length.

4.Operating voltage DC220V.

5.Other requirements shall be subject to the contents confirmed in the order selection table.

6.Technical parameters are subject to the instruction manual.

Rated current(A)

630

1250

1600

2000

2500

3150

Rated short-circuit breaking current (kA)

25,31.5

31.5

Size of mating stationary contact (mm)

φ35

φ49

φ55

φ79

φ90

φ109

 

Handcart standard wiring(165)

-59

-1

Hot Tags: zn85- 40.5 indoor high voltage vacuum circuit breaker, High Voltage and Low Voltage Switchgear Series, SF6-40.5 Indoor Sulfur Hexafluoride Circuit Breaker, LN2-35 Indoor Sulfur Hexafluoride Circuit Breaker, ZN12 12 Vacuum Circuit Breaker, ZW32-40.5 Outdoor Vacuum Circuit Breaker, LW16 40 5 Outdoor Sulfur Hexafluoride Circuit Breaker

Send Inquiry

whatsapp

Phone

E-mail

Inquiry