ERW1-1600 Universal Circuit Break
Scope of application
ERW1-1600 (DW50) universal circuit breaker (hereinafter referred to as circuit breaker) has a rated current of 200A to 1000A, and a rated working voltage of AC400V, 690V, 50Hz.
It is mainly used in power distribution networks to distribute electric energy and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding and other faults. Under normal conditions, it can also be used for infrequent line conversion. It can provide selective protection and precise action, avoid unnecessary power outages, and improve the reliability of power supply.
It meets the standards: GB/T14048.2, IEC60947-2.
Model meaning

Normal working conditions and installation conditions
a. Ambient temperature
1. The upper limit of the ambient air temperature shall not exceed +40℃, the lower limit shall be -5℃, and the average temperature value within 24 hours shall not exceed +35℃ (unless otherwise specified)
2. For use in ambient air temperature higher than +40℃, the maximum ambient temperature allowed is +60°C according to Table 1 and the capacity reduction. (Refer to Table 1 for the requirements of capacity reduction)
b. Altitude
The altitude of the installation site shall not exceed 2000m; (if it exceeds 2000m, the capacity reduction shall be used, and the requirements of capacity reduction shall refer to Table 2)
c. Limit and atmospheric conditions
When the relative humidity of the atmosphere is within the range of +40℃, the relative humidity of the air shall not exceed 50%. Higher relative humidity can be allowed at lower temperatures, for example, the humidity can reach 90% at 20℃. Special measures should be taken for condensation caused by temperature changes.
d. The pollution level is level 3.
e. Use category B
f. Installation category
1. Circuit breaker installation category IV When the rated working voltage of the main circuit is less than AC400V, the auxiliary circuit installation category is the same as the circuit breaker except for the undervoltage release coil and the booster or power module primary coil used for the intelligent controller. When the rated working voltage of the main circuit is greater than AC and less than or equal to AC690V, the auxiliary circuit needs to be isolated from the main circuit by a transformer. The isolation transformer has a capacity of ≥2kVA and the maximum working voltage of the control circuit is AC400V. The auxiliary circuit installation category is IⅢ.
2. Installation conditions. The circuit breaker should be installed according to the requirements of this manual, and its vertical inclination should not exceed 5.
Product Parameters
| Frame grade Rated current | 1600 | ||
| Rated operating current In(A) | 200/250/300/350/400/500/630/700/800/1000 | ||
| Level | 3P/4P | ||
| Frequency(Hz) | 50 | ||
| Rated operating voltage Ue (V) | 400/690 | ||
| Rated insulation voltage Ui (V) | 1000 | ||
| Rated impulse withstand voltage Uimp (kV) | 12 | ||
| Breaking capacity level | Empty (Normal) | ||
| Rated ultimate circuit breaking capacity Icu(kA) | AC400V | 55 | |
| AC690V | 25 | ||
| Rated operating circuit breaking capacity IcS(kA) | AC400V | 42 | |
| AC690V | 20 | ||
| Rated short-time withstand current Icw/ls(kA) | AC400V | 42 | |
| AC690V | 20 | ||
| Service life | Mechanical | Maintenance-free 3000 Maintenance-required 10000 | |
| Electrical | Maintenance-free 1000 | ||
| Arcing distance (mm) | 0 | ||
| Installation method | Fixed/Drawer type | ||
| Wiring method | Horizontal, vertical | ||
| Controller type | M 2H 3M 3H | ||
| Net weight (kg) | Drawer type three-pole/four-pole | 38 | 55 |
| Fixed type three-pole/four-pole | 22 | 26.5 | |
Dimensions
| Model | ERW1-1600 |
| Fixed 3P | 280×289×315 |
| Fixed 4P | 350×389×315 |
| Drawer 3P | 305×373×362 |
| Drawer 4P | 375×373×362 |
1.Derating (derating at different temperatures)
| Ambient temperature | +40℃ | +45℃ | +50℃ | +55℃ | +60℃ | |
| Allowable continuous working current | ERW1-200/400 | IIn | 0.95In | 0.9In | 0.85In | 0.80In |
| ERW1-630 | IIn | 0.95In | 0.9In | 0.85In | 0.80In | |
| ERW1-800/1000 | IIn | 0.95In | 0.9In | 0.85In | 0.80In | |
2. Capacity reduction requirements at different altitudes
When the altitude exceeds 2000 meters, the insulation performance and pressure in the atmosphere will change. For other parameters, refer to the following
a. Voltage
| Altitude | Power frequency withstand voltage (V) | Insulation voltage (V) | Rated working voltage (V) |
| 2000 | 2200 | 1000 | 690 |
| 3000 | 1955 | 800 | 580 |
| 4000 | 1760 | 700 | 500 |
| 5000 | 1600 | 600 | 400 |
b. Voltage
| Altitude (m) | Rated operating current (LE) |
| 2000 | le |
| 2500 | 0.93le |
| 3000 | 0.88le |
| 3500 | 0.83le |
| 4000 | 0.78le |
| 4500 | 0.73le |
| 5000 | Must contact 2T |
1600 H-type, communication controller secondary wiring diagram

Communication controller secondary wiring diagram terminal description
| Separator | Function Description | Remarks |
| 41,42 | Auxiliary power input | Basic configuration (factory default) |
| 43,44,45 | Fault trip contact output (4# is common terminal) |
Basic configuration (factory default)
|
| 46,47 | Circuit breaker status auxiliary contact 1 output | |
| 48,49 | Circuit breaker status auxiliary contact 2 output | |
| 60 | Protective earth (PE) | |
| 50,51 | RS485 communication interface leads to A and B terminals | |
| 52,53 | Relay (DO1) contact output | |
| 54,55 | Relay (DO2) contact output | |
| 56,57 | Remote control opening control output (D03 bidirectional thyristor controls pure electromagnetic coil) | |
| 58,59 | Remote control closing control output (D04 bidirectional thyristor controls pure electromagnetic coil) | |
| 61,62,63,64 | Voltage measurement input: N, A, B, C | |
| 65,66 | Connect neutral line transformer for 3P+N structure and connect leakage transformer ZCT1 for leakage protection | Ordering instructions |
Usage Tips
Q-undervoltage release (can be connected in series with the "emergency stop" button when in use);
F-shunt release (can be connected in series with the normally open auxiliary contact when in use)
X-closing electromagnet (can be connected in series with the normally closed auxiliary contact when in use);
M-energy storage motor; SB2-manual opening button; SB1-manual closing button;

DF-circuit breaker auxiliary switch (6 groups of conversion)
Q-undervoltage voltage (instantaneous or delayed)
5A-motor travel switch
#41, 42-auxiliary power input (AC and DC universal)
SB1-shunt button (user-prepared)
F-shunt release
XT-terminal
#43, 44, 45-fault trip contact output terminal, 44 is the common point
X-closing electromagnet
0-signal light (user-prepared)
#46, 47, 48, 49-circuit breaker status auxiliary point output terminal.
FU-fuse
58-can be directly connected to the power supply (automatic pre-energy storage), or can be connected in series with the normally open button and then connected to the power supply (manual pre-energy storage)
SB3-undervoltage button (user-prepared)
SB2-closing button
M-energy storage motor
Note: power supply --- if the rated voltage of Q, F, X, etc. is different, different currents should be connected respectively (the dotted part is connected by the user)
Installation dimensions and external dimensions
1. Installation dimensions and external dimensions of fixed circuit breakers


2. Installation dimensions and overall dimensions of drawer-type circuit breakers



About Us
Shaanxi Huadian Electric Co., Ltd. is a leading manufacturer of electrical equipment, specializing in Vacuum circuit breakers,Vacuum Interrupter,High Voltage And Low Voltage Switchgear Series,VCB Accessory Device,And Various Small Circuit Breakers,Plastic Case Circuit,Isolating Switch,AC Contactor,Etc.. We are committed to providing high-quality, reliable, and cost-effective solutions to our global partners.
OEM Services
We offer comprehensive OEM services to meet your specific needs, including:
Product Design and Development: Our experienced engineering team can work with you to design and develop customized electrical equipment tailored to your requirements.
Manufacturing and Assembly: We utilize advanced manufacturing facilities and strict quality control processes to ensure the highest standards of production.
Branding and Packaging: We can accommodate your branding and packaging preferences to create a seamless product experience for your customers.
Logistics and Delivery: We offer flexible logistics solutions to ensure timely delivery of your orders worldwide.
Why Choose Us
Extensive Experience: With years of experience in the electrical equipment industry, we have the expertise to deliver exceptional OEM services.
Advanced Technology: We invest in cutting-edge technology and equipment to ensure the quality and efficiency of our manufacturing processes.
Competitive Pricing: We offer competitive pricing without compromising on quality, providing you with the best value for your investment.
Excellent Customer Service: Our dedicated team is committed to providing you with prompt and professional service throughout the entire process.
Contact Us
For inquiries about our OEM services or to discuss your specific requirements, please feel free to contact us:
We look forward to hearing from you and exploring how we can collaborate to achieve mutual success.
Our factory



Our Certificate




Hot Tags: erw1-1600 universal circuit break, rom, fiber optic splitters, memory chips, ldrs, infrared sensors, rf antennas
Previous
No InformationYou Might Also Like
Send Inquiry