12~40.5KV Circuit Breaker Embedded Poles

12~40.5KV Circuit Breaker Embedded Poles

Overview The 12-40.5kV sealed pole for circuit breakers is a key component used in medium and high voltage circuit breakers, mainly used for isolation and arc extinguishing. The sealed pole uses solid insulating materials (such as epoxy resin) to encapsulate the conductive part and arc...
Send Inquiry
Product Introduction

 

Overview

 

The 12-40.5kV sealed pole for circuit breakers is a key component used in medium and high voltage circuit breakers, mainly used for isolation and arc extinguishing. The sealed pole uses solid insulating materials (such as epoxy resin) to encapsulate the conductive part and arc extinguishing chamber of the circuit breaker together. It has high insulation, weather resistance and mechanical strength, and is suitable for power systems with voltage levels of 12kV to 40.5kV.

 

Main features


★High insulation performance:

The sealed pole uses solid insulating materials such as epoxy resin, which has excellent insulation performance and can effectively prevent the influence of the external environment (such as humidity, dust, etc.) on the equipment.

★Compact design:

The sealed pole integrates the conductive part and the arc extinguishing chamber, with a compact structure, which reduces the volume and weight of the equipment and is easy to install and maintain.

★High reliability:

The solid insulating material has good aging resistance and weather resistance, can operate stably for a long time in harsh environments, and reduce the failure rate.

★Environmental protection:

The sealed pole does not use SF6 gas, avoids the emission of greenhouse gases, and meets environmental protection requirements.

★Maintenance-free:

Due to the use of solid insulating materials, the sealed poles require almost no maintenance, reducing operating costs.

 

Application scenarios


The sealed poles are widely used in the following fields:

★Substations: used in distribution systems with voltage levels of 12kV to 40.5kV.

★Industrial power systems: suitable for power protection in industrial sites such as factories and mines.

★Urban distribution networks: used for power distribution and protection of urban power grids.

★New energy fields: protection of new energy power generation systems such as wind farms and photovoltaic power stations.

 

Technical Parameter

 

12KV: EP12-630-25,EP12/1250-25, EP12/1250-31.5
product-652-641 product-1-1
parameter name parameter
Rated voltage 12kV
Rated current 630/1250A
Rated frequency 50Hz
Rated short-duration power frequency withstand voltage (1min) 48kV
Rated lightning impulse withstand voltage 85kV
Rated short-circuit breaking current 25/31.5kA
Rated peak withstand current 63/80KA
Rated short-circuit making current (peak value) 63/80KA
Rated short-circuit breaking current breaking times 30 times
Rated back-to-back capacitor bank breaking current* 400A
Rated single capacitor bank breaking current* 630A
Rated short-time withstand current 25/31.5kA
Mechanical life 30000 times
Contact self-closing force 100±30N
Contact reaction force at rated opening distance 200±30N
Loop resistance at lower limit of rated working pressure ≤25μ Ω
Storage period 20 years
Contact allowable wear thickness 3mm
Moving part weight ≤2.5kg

Mechanical parameters of the matched vacuum switch

parameter name parameter
Contact distance 9±1mm
Rated contact travel 4±1mm
Average opening speed 1.1±0.2m/s
Average closing speed 0.6±0.2m/s
Rated contact pressure 2000±200N
Contact closing bounce time ≤2ms
Contact opening rebound amplitude ≤2mm
Different phases of opening and closing of contacts ≤1ms

Note: * is the rated value provided upon request

24KV: EP24/1250-31.5, EP24/1600-31.5
product-675-663 product-1-1
parameter name parameter
Rated voltage 24kV
Rated current 1250/1600A
Rated frequency 50Hz
Rated short-duration power frequency withstand voltage (1min) 65/79kV
Rated lightning impulse withstand voltage 125kV
Rated short-circuit breaking current 31.5kA
Rated peak withstand current 80KA
Rated short-circuit making current (peak value) 80KA
Rated short-circuit breaking current breaking times 30 times
Rated back-to-back capacitor bank breaking current* 400A
Rated single capacitor bank breaking current* 630A
Rated short-time withstand current 31.5kA
Mechanical life 30000 times
Contact self-closing force 100±30N
Contact reaction force at rated opening distance 200±30N
Loop resistance at lower limit of rated working pressure ≤25μΩ
Storage period 20 years
Contact allowable wear thickness 3mm
Moving part weight ≤2kg

Mechanical parameters of the matched vacuum switch

parameter name parameter
Contact distance 12±1mm
Rated contact travel 4±1mm
Average opening speed 1.1±0.2m/s
Average closing speed 0.8±0.2m/s
Rated contact pressure 2500±200N
Contact closing bounce time ≤2ms
Contact opening rebound amplitude ≤2mm
Different phases of opening and closing of contacts ≤2ms

Note: * is the rated value provided upon request

24KV: EP24/630-20, EP24/1250-25
product-648-653 product-580-753
parameter name parameter
Rated voltage 24kV
Rated current 630/1250A
Rated frequency 50Hz
Rated short-duration power frequency withstand voltage (1min) 65/79kV
Rated lightning impulse withstand voltage 125kV
Rated short-circuit breaking current 20/25kA
Rated peak withstand current 50/63KA
Rated short-circuit making current (peak value) 50/63KA
Rated short-circuit breaking current breaking times 30 times
Rated back-to-back capacitor bank breaking current* 400A
Rated single capacitor bank breaking current* 630A
Rated short-time withstand current 25/31.5kA
Mechanical life 30000 times
Contact self-closing force 100±30N
Contact reaction force at rated opening distance 200±30N
Loop resistance at lower limit of rated working pressure ≤25μΩ
Storage period 20 years
Contact allowable wear thickness 3mm
Moving part weight ≤2kg

Mechanical parameters of the matched vacuum switch

parameter name parameter
Contact distance 13±1mm
Rated contact travel 4±1mm
Average opening speed 1.1±0.2m/s
Average closing speed 0.8±0.2m/s
Rated contact pressure 2400±200N
Contact closing bounce time ≤2ms
Contact opening rebound amplitude ≤2mm
Different phases of opening and closing of contacts ≤2ms

Note: * is the rated value provided upon request

24KV: EP24/2000-31.5
product-573-614 product-550-734
parameter name parameter
Rated voltage 24kV
Rated current 2000A
Rated frequency 50Hz
Rated short-duration power frequency withstand voltage (1min) 65kV
Rated lightning impulse withstand voltage 125kV
Rated short-circuit breaking current 31.5kA
Rated peak withstand current 80KA
Rated short-circuit making current (peak value) 80KA
Rated short-circuit breaking current breaking times 30 times
Rated back-to-back capacitor bank breaking current* 400A
Rated single capacitor bank breaking current* 630A
Rated short circuit duration 4S
Mechanical life 10000 times
Contact self-closing force 200±30N
Contact reaction force at rated opening distance 320±30N
Loop resistance at lower limit of rated working pressure ≤25μΩ
Storage period 20 years
Contact allowable wear thickness 3mm
Moving part weight 3.8±0.3 Kg

Mechanical parameters of the matched vacuum switch

parameter name parameter
Contact distance 13±1mm
Average opening speed 1.4±0.2m/s
Average closing speed 0.8±0.2m/s
Rated contact pressure 3200±300N
Contact closing bounce time ≤2ms
Contact opening rebound amplitude ≤2mm

Note: * is the rated value provided upon request

40.5KV: EP40.5/1600-25, EP40.5/2000-25, EP40.5/1600-31.5, EP40.5/2000-31.5
  40.5 Kv Embedded Pole For Vacuum Circuit Breaker product-1-1
parameter name parameter
Rated voltage 40.5kV
Rated current 1600/2000A
Rated frequency 50Hz
Rated short-duration power frequency withstand voltage (1min) 95kV
Rated lightning impulse withstand voltage 185kV
Rated short-circuit breaking current 25/31.5kA
Rated peak withstand current 80KA
Rated short-circuit making current (peak value) 80KA
Rated short-circuit breaking current breaking times 30 times
Rated back-to-back capacitor bank breaking current* 400A
Rated single capacitor bank breaking current* 630A
Rated short-time withstand current 25/31.5kA
Mechanical life 10000 times
Contact self-closing force 250±60N
Contact reaction force at rated opening distance 340±60N
Loop resistance at lower limit of rated working pressure ≤25μ Ω
Storage period 20 years
Contact allowable wear thickness 3mm
Moving part weight ≤1.7kg

Mechanical parameters of the matched vacuum switch

parameter name parameter
Contact distance 18±1mm
Rated contact travel 4±1mm
Average opening speed 1.7±0.2m/s
Average closing speed 0.8±0.2m/s
Rated contact pressure 3200±200N
Contact closing bounce time ≤3ms
Contact opening rebound amplitude ≤2mm
Different phases of opening and closing of contacts ≤1ms

Note: * is the rated value provided upon request

40.5KV: EP40.5/1250-31.5
product-671-648 product-502-716
parameter name parameter
Rated voltage 40.5kV
Rated current 1250A
Rated frequency 50Hz
Rated short-duration power frequency withstand voltage (1min) 95kV
Rated lightning impulse withstand voltage 185kV
Rated short-circuit breaking current 31.5kA
Rated peak withstand current 80KA
Rated short-circuit making current (peak value) 80KA
Rated short-circuit breaking current breaking times 30 times
Rated back-to-back capacitor bank breaking current* 400A
Rated single capacitor bank breaking current* 630A
Rated short circuit duration 4S
Mechanical life 10000 times
Contact self-closing force 110±40N
Contact reaction force at rated opening distance 210±40N
Loop resistance at lower limit of rated working pressure ≤25μ Ω
Storage period 20 years
Contact allowable wear thickness 3mm
Moving part weight 6.8±0.3 Kg

Mechanical parameters of the matched vacuum switch

parameter name parameter
Contact distance 18±1mm
Average opening speed 1.7±0.3m/s
Average closing speed 1.3±0.2m/s
Rated contact pressure 3500±300N
Contact closing bounce time ≤3ms
Contact opening rebound amplitude ≤3mm

Note: * is the rated value provided upon request

40.5KV: EP40.5/2500-31.5
product-600-655 product-490-722
parameter name parameter
Rated voltage 40.5kV
Rated current 2500A
Rated frequency 50Hz
Rated short-duration power frequency withstand voltage (1min) 95kV
Rated lightning impulse withstand voltage 185kV
Rated short-circuit breaking current 31.5kA
Rated peak withstand current 80KA
Rated short-circuit making current (peak value) 80KA
Rated short-circuit breaking current breaking times 30 times
Rated back-to-back capacitor bank breaking current* 400A
Rated single capacitor bank breaking current* 630A
Rated short circuit duration 4S
Mechanical life 10000 times
Contact self-closing force 200±40N
Contact reaction force at rated opening distance 400±40N
Loop resistance at lower limit of rated working pressure ≤25μ Ω
Storage period 20 years
Contact allowable wear thickness 3mm
Moving part weight 7.8±0.3 Kg

Mechanical parameters of the matched vacuum switch

parameter name parameter
Contact distance 18±1mm
Average opening speed 1.7±0.3m/s
Average closing speed 1.3±0.2m/s
Rated contact pressure 3500±300N
Contact closing bounce time ≤3ms
Contact opening rebound amplitude ≤3mm

Note: * is the rated value provided upon request

 

Advantages


★High safety: Solid insulation materials avoid the risk of gas leakage and improve the safety of equipment.

★Long life: The design life of the sealed pole can usually reach more than 20 years.

★Strong adaptability: Suitable for various complex environments, such as high altitude, high humidity, high pollution, etc.

 

Our factory
ZN28-12 Vacuum Circuit Breaker in stock
bulk ZN28-12 Vacuum Circuit Breaker
ZN28-12 Vacuum Circuit Breaker price

Our Certificate

 

 

1

3

        8

46

 

 

 

Contact us

 

If you need to contact us for more information, support, or inquiries, please use the following details:pannie@hdswitchgear.com.

 

 

Hot Tags: 12~40.5kv circuit breaker embedded poles, embedded street pole, embedded hinge pole, embedded collapsible pole, embedded assembly pole, adjustable pole embedded, construction pole embedded

Send Inquiry

whatsapp

Phone

E-mail

Inquiry