ZN85-40.5KV Indoor HV Vacuum Circuit Breaker
Selection

Product technical features
Integrated and modular design
The overall structure of the circuit breaker is simple and reasonable, and the arc extinguishing chamber part, interlocking part and operating part are arranged up and down.
The dedicated spring operating mechanism does not need to be adjusted, and the action is stable and reliable.
The installation form is free and flexible, including the installation in the drawer-type cabinet and the fixed installation of the side mechanism arrangement
High reliability insulation tube
The insulation tube is made of epoxy resin with reliable electromechanical performance through mature vacuum casting process.
The vacuum arc extinguishing chamber is arranged in a closed insulation tube, which significantly improves the insulation performance, and is affected by the harsh external environment, effectively preventing dust and foreign matter from entering the main circuit part.
Significantly reduce the overall size of the circuit breaker.
Advanced vacuum interrupter
WL-35855X vacuum interrupter is the first choice, with quality assurance from Cutler-Hammar of the United States.
Optional coil-type longitudinal strong magnetic field structure vacuum interrupter, using ceramic shell, copper-chromium contact material, small size, high insulation level, strong arc extinguishing ability, long electrical life, excellent breaking and closing short-circuit current performance.
Optional solid sealing process
The main conductive circuit of the circuit breaker adopts solid sealing process, and the vacuum interrupter is cast in the insulation.
The insulation strength is greatly improved.
Environmental resistance is significantly enhanced.
Operating Conditions
1.The ambient air temperature does not exceed +40'C, and the mean value measured within 24h does notexceed 35'C, and the min. ambient air temperature is -15°C;
2. Altitude: 1.000 meters.
3.There is no obvious pollutions such as dust, smoke, corrosion or flammable gas, steam gas, or salt sprayin the ambient air.
4. Humidity conditions: The daily mean is not greater than 95%%, and the monthly mean is not greater than90%: the mean value of water steam pressure is not greater than 2.2KPa, and the monthly mean of wateisteam pressure is not greater than l.&kPa:
5. Vibration or earthquake from the outside ofthe switchgear or controlgear can be omitted,
6. T'he magnitude of the electromagnetic interference induced in the secondary system does not exceed 1.6kV.
7. Special working conditions
If installed at the place where the alitude exceeds 1.000 meters, the ambient air temperature is out ofthe limit value specifed by the normal working conditions or condensation may easily occur due to highhumidity, please contact our company for customization.
Main technical parameters
| No. | Name | Unit | Data | |
| 1 | Rated voltage | KV | 40.5 | |
| 2 | Rated insulation level | 1min power frequency withstand voltage (effective value) | KV | 95 |
| rated lightning impulse withstand voltage (effective value) | KV | 185 | ||
| 3 | Rated current | A | 630 1250 1600 2000 | |
| 4 | Rated frequency | Hz | 50 | |
| 5 | Rated short-time withstand current | KA | 20 25 31.5 | |
| 6 | Rated peak withstand current | KA | 50 63 80 | |
| 7 | Rated short-circuit breaking current | KA | 20 25 31.5 | |
| 8 | Rated short-circuit breaking current (peak value) | KA | 50 63 80 | |
| 9 | Rated short-circuit duration | S | 4 | |
| 10 | Rated operation sequence | O-0.3s-CO-180s-CO | ||
| 11 | Breaking time | ms | <80 | |
| 12 | Rated short-circuit breaking current breaking times | time | 20 | |
| 13 | Rated capacitor bank breaking current | A | 400 | |
| 14 | Mechanical life | time | 10000 | |
| 15 | Rated operating voltage | V | ﹣110/~110,﹣220/~220 |
Appearance and installation dimensions:
KYN61-40.5 with cabinet width 1400mm uses ZN85-40.5

KYN61-40.5 with cabinet width of 1680mm uses ZN85-40.5

Solid sealed pole type ZN85-40.5

ZN85-40.5 side mounted circuit breaker

Contact us
For more detailed information or technical consultation, please contact us:pannie@hdswitchgear.com.
Our factory



Our Certificate





Hot Tags: zn85-40.5kv indoor hv vacuum circuit breaker, high voltage vacuum circuit breaker indoor parameter, technical specification of indoor high voltage vacuum circuit breaker
You Might Also Like
Send Inquiry